Frequency-Constrained Unit Commitment Using Offline Frequency-Response Screening

Huy Nguyen Duc1, , Cuong Hoang Anh1, Anh Phung Van1, Alexander Vo1
1 Ha Noi University of Science and Technology, Ha Noi, Vietnam

Main Article Content

Abstract

This paper presents a frequency-constrained unit commitment (FCUC) framework in which post-contingency rate-of-change-of-frequency (RoCoF) and frequency-nadir criteria are translated into generator-commitment constraints. For each system, offline screening of commitment states using a center-of-inertia (COI)-based average system frequency response (ASFR) model identifies minimum requirements for equivalent inertia, a turbine-response index, and inverse droop. These requirements are imposed as linear constraints, preserving the mixed-integer linear programming (MILP) formulation. The framework is evaluated on the IEEE 39-bus and WECC-179 systems. For WECC-179, Ward-based Q–V zoning and area-level reactive-power balance constraints are also included as a surrogate for reactive-power adequacy. COI/ASFR post-checks show that the FCUC schedules satisfy the design-contingency criteria within the screening model. For IEEE 39, under a 0.60 Hz/s RoCoF limit, FCUC commits all 10 units, compared with 7–9 under conventional UC, with a 2.79% increase in scheduling cost. For WECC-179, scheduling raises the UC-to-FCUC objective from 14.323 to 14.929 million USD (+4.229%). Independent ANDES time-domain simulations for the loss of G2 show that FCUC reduces the worst-case RoCoF from 0.64 to 0.49 Hz/s and raises the minimum nadir from 59.78 to 59.79 Hz. Taken together, these results demonstrate that interpretable aggregate frequency-response requirements can be embedded in UC while retaining its MILP structure and explicitly revealing the trade-off between scheduling cost and post-contingency frequency security.

Article Details

References

[1] J.-J. Wu, G. W. Chang, C. Sinatra, and P.-Y. Tsai, Unit commitment with frequency stability enhancement for an isolated power system, IEEE access : practical innovations, open solutions, vol. 12, pp. 91396–91409, Jul. 2024. https://doi.org/10.1109/ACCESS.2024.3421628
[2] X. Liu, X. Fang, N. Gao, H. Yuan, A. Hoke, H. Wu, and J. Tan, Frequency nadir constrained unit commitment for high renewable penetration island power systems, IEEE Open Access Journal of Power and Energy, vol. 11, pp. 141–153, Feb. 2024. https://doi.org/10.1109/OAJPE.2024.3370504
[3] G. Yan, L. Yan, Y. Meng, J. Han, and Z. Li, Linearexponential decay frequency curve for unit-specific response in frequency-constrained unit commitment, IEEE Transactions on Power Systems, vol. 41, iss. 5, pp. 3548–3565, Sep. 2026. https://doi.org/10.1109/TPWRS.2026.3685128
[4] L. Badesa, F. Teng, and G. Strbac, Optimal portfolio of distinct frequency response services in low-inertia systems, IEEE Transactions on Power Systems, vol. 35, iss. 6, pp. 4459–4469, Nov. 2020. https://doi.org/10.1109/TPWRS.2020.2997194
[5] R. Shikuma, Y. Fujimoto, D. Orihara, H. Kikusato, H. Taoka, and Y. Hayashi, Impact of virtual synchronous generators on frequency-constrained unit commitment: a neural network-assisted framework for assessing rate of change of frequency, IEEE access : practical innovations, open solutions, vol. 13, pp. 117716–117731, Jul. 2025. https://doi.org/10.1109/ACCESS.2025.3585194
[6] L. Badesa, F. Teng, and G. Strbac, Conditions for regional frequency stability in power system scheduling—Part II: Application to Unit Commitment, IEEE Transactions on Power Systems, vol. 36, iss. 6, pp. 5567–5577, Nov. 2021. https://doi.org/10.1109/TPWRS.2021.3073077
[7] M. Tuo and X. Li, Security-constrained unit commitment considering locational frequency stability in low-inertia power grids, IEEE Transactions on Power Systems, vol. 38, iss. 5, pp. 4134–4147, Sep. 2023. https://doi.org/10.1109/TPWRS.2022.3215915
[8] S. Zhao, Z. Wei, Y. Fang, X. Liu, and S. Sun, Frequency constrained unit commitment under multi-uncertainty: a robust and non-anticipative implicit decision method, CSEE Journal of Power and Energy Systems, 2026. https://doi.org/10.17775/CSEEJPES.2024.06570
[9] Y. Yuan, Y. Cao, Z. Zhang, W. Hu, and Z. Chen, Refined frequency-constrained unit commitment under converter-induced uncertain-variability through bayesian filtering, IEEE Transactions on Power Systems, vol. 41, iss. 5, pp. 3302–3322, Sep. 2026.
https://doi.org/10.1109/TPWRS.2026.3684036
[10] Q. Shi, Y. Zhu, K. Fan, R. Cheng, J. Shen, and W. Liu, Two-stage linearization of frequency nadir constraint for unit commitment, IEEE Transactions on Power Systems, vol. 40, iss. 4, pp. 3584–3587, Jul. 2025. https://doi.org/10.1109/TPWRS.2025.3564110
[11] M. Rajabdorri, E. Lobato, L. Sigrist, and J. Aghaei, Data-driven continuous-time framework for frequencyconstrained
unit commitment, International Journal of Electrical Power & Energy Systems, vol. 162, Nov. 2024, Art. no. 110327. https://doi.org/10.1016/j.ijepes.2024.110327
[12] A. O. Olasoji, D. T. O. Oyedokun, M. Rajabdorri, J. E. Sierra-Aguillar, C. E. Okafor, M. Mditshwa, and K. A. Folly, Frequency-Constrained Unit Commitment Using SODE-labelled Affine Surrogates, in 2026 8th Global Power, Energy and Communication Conference (GPECOM), pp. 703–708, Jun. 2026.
[13] S. H. Beigi Fard, M. R. Shakarami, and M. Doostizadeh, Frequency-constrained robust unit commitment via physics-guided piecewise-linear nadir surrogates and adaptive virtual inertia, Scientific Reports, vol. 16, Mar. 2026, Art. no. 14305.
https://doi.org/10.1038/s41598-026-43137-z
[14] Y. Wen, W. Li, G. Huang, and X. Liu, Frequency Dynamics constrained unit commitment with battery energy storage, IEEE Transactions on Power Systems, vol. 31, iss. 6, pp. 5115–5125, Nov. 2016. https://doi.org/10.1109/TPWRS.2016.2521882
[15] B. Jiang, C. Guo, and Z. Chen, Frequency constrained unit commitment considering reserve provision of wind power,
Applied Energy, vol. 361, May 2024, Art. no. 122898. https://doi.org/10.1016/j.apenergy.2024.122898
[16] M. Sarvarizadeh, M. Rajabdorri, E. Lobato, and L. Sigrist, A Comparative Study on Frequency-Constrained Unit Commitment Approaches in Island Power Systems, arXiv preprint arXiv:2507.05079, Jul. 2025.
[17] H. Cui, F. Li, and K. Tomsovic, Hybrid symbolic-numeric framework for power system modeling and analysis, IEEE
ransactions on Power Systems, vol. 36, iss. 2, pp. 1373–1384, Mar. 2021. https://doi.org/10.1109/TPWRS.2020.3017019